fa_logo

Programmable Controllers MELSEC-A Series

Renewal

img-mv-1-sm

Replace with the Q Series CPU module while keeping the existing modules

Upgrade example

QA Extension Base Unit (QA1S51B)

Supported series: AnS/QnAS

Replace the AnS/QnAS Series CPU with the Q Series CPU while keeping the existing AnS/QnAS Series modules

Gradual transition from the AnS/QnAS Series to the Q Series (Q mode)

  • Construct a system that is controlled by the new Q Series CPU (Q mode) while keeping the existing AnS/QnAS Series modules installed to a QA1S□B extension base unit. The AnS/QnAS Series modules can gradually be replaced to comprise a Q Series-only system at the end.
    qa1s_expansin_illst01
  • The QA1S□B extension base units are compatible with the Universal model QCPUs*1 (including the High-speed Universal model QCPUs). Process CPUs, redundant CPUs, Safety CPUs and remote I/O Stations are not compatible.
  • Some modules are not installable on the QA1S□B extension base unit. For details, please refer to the "QCPU User's Manual (Hardware Design, Maintenance and Inspection) (SH(NA)-080473ENG)".
  • No further extensions can be made to QA1S51B because QA1S51B is not equipped with an extension cable connector.

*1.The Universal model QCPU of which first 5-digit serial number is 13102 or later, is compatible with the base units.

Reduce conversion effort by using the same I/O addresses

  • When utilizing existing modules with a Q Series CPU, it is not required to change the I/O number of the existing modules. For new module(s) on the main base unit, assign a subsequent number, which comes after the existing module numbers in the I/O assignment settings. This can greatly reduce the program modification time.
    qa1s_expansin_illst02

Note:Assign the I/O numbers in the following order: Q Series to AnS/QnAS Series or AnS/QnAS Series to Q Series.
When the order is mixed (i.e., Q Series → AnS/QnAS Series → Q Series), an error will occur in the CPU.

Example of I/O assignment

    Modelo Tipo Point Address
Main
base
unidad
0 QJ61BT11N Inteligente 32 100
1 QJ71LP21-25 Inteligente 32 120
2 QX41 Entrada 32 140
3 QX41 Entrada 32 160
4 QY41P Salida 32 180
    Modelo Tipo Point Address
Extensión
base
unidad
5 A1SX41 Entrada 32 00
6 A1SY41P Salida 32 20
7 - Empty 32 40
8 - Empty 32 60
9 A1SX41 Entrada 32 80

Related documents

Manual de transición de la serie MELSEC-AnS/QnAS (pequeños) a la serie Q (principios básicos)
2021-03